Procom Controls

Occupancy Light Level Dimming

Commissioning -  Light Level Only

ProLux-Light Level Only

PROLUX - Commissioning

 

 

The Prom 1,2 or 3 are system controllers which provide power to remote photocell detectors. The units contain up to three 6 Amp switching relays.

 

 

 

 

 

Remote Control Set-UP

 

Important

The infra red receiver is located within the Prolux sensor head.

The remote control set up tool has a range of 2 – 3 metres and should be aimed directly at the prolux sensor to activate commissioning process.

When first powered up sensors will take approximately 15 minutes to stabilise before normal operation commences and set-up can take place.

 

Commissioning

In normal operation the LED is off

 

Setting A Light Level

Remember you set the level at the point you wish lighting to switch on therefore if it becomes brighter from that setting lighting will switch off and if it gradually becomes darker they will remain on

 

Ensure that the lighting you are setting is off by toggling the right hand blue button

 

Step One

Ensure lighting is switched off using the right hand blue button.

A press of the left red button puts the unit into light level enabled mode a red LED will flash continuously.

 

Step Two

With the red LED constantly flashing press the blue right button to store

the current ambient light level, the led will go off and the fluorescent lighting will switch on [this is the level that lights will switch on] Light level is set when natural daylight levels are at the point you wish lights to switch on.

 

Important Note.

It is possible to permanently override the unit on or off by pressing the right hand blue button. If this is done it is imperative to de-latch this setting to put the unit back into automatic mode.

 

To de-latch back into automatic mode - Ensure the lighting is on if off override on by pressing the blue left-hand button. Press the left red button once so the red Led is flashing and then press the right hand blue button once |the Led will go out and the unit will be de-latched].

 

If you do the above with the lighting switched off you will have de-latched and set a new lights on level.

 

Alternatively switch the power off to the Prolux unit via the MCB supply point and reinstate MCB to de-latch the unit back into its pre-set automatic mode.